-
Improperly compacted backfill and
fill present around the foundation. All backfill and fill should be
placed in 6" to 8" layers and tamped for proper compaction.
This could allow items like the driveway, sidewalk and front porch
steps to settle. (1995 CABO 1 & 2 Family Dwelling Code, Section
406.3.4)
-
Grading does not slope away from the
foundation. Lots should be graded to drain surface
water away from foundation walls. The grade away from foundation walls
shall fall a minimum of 6" within the first 10 feet. (1995 CABO
1 & 2 Family Dwelling Code, Sections 401.3 & 406.3.5)
-
Grading might hold ground water.
The code requires all drainage to be diverted away from the
yard. Surface drainage shall be diverted to a storm sewer conveyance
or other point of collection. (1995 CABO 1 & 2 Family Dwelling
Code, Section 401.3)
-
Foundations with improperly compacted
fill. Could probe under the footings.
Fills which support footings and foundations shall be designed, installed
and tested in accordance with accepted engineering practices. (1995
CABO 1 & 2 Family Dwelling Code, Section 401.2)
-
No vapor barrier present for a concrete
slab. This could allow water or moisture problems
in the basement. A vapor barrier is required under all interior slabs
except garages. (1995 CABO 1 & 2 Family Dwelling Code, Section
505.2.3)
-
Improper wall bracing for a 1 or 2
story structure. The corner exterior walls are missing
proper bracing. Exterior walls shall be braced at each corner and
at least every 25 feet with approved structural sheathing or
1x4 let-in braces or approved metal straps diagonally tied
from the bottom plate to the top plate. (1995 CABO 1 & 2 Family
Dwelling Code, Table 602.9)
-
Improper wall bracing for a 3 story
structure. The corner exterior walls
are missing proper bracing. All exterior corner walls shall be braced
at each corner and at least every 25 feet with a minimum of 48"
of approved structural sheathing. (1995 CABO 1 & 2 Family Dwelling
Code, Table 602.9)
-
Exterior windows and doors do not have
properly installed flashing and weep holes at the
brick. Flashing is required above all doors and windows installed
in brick and prevents water from soaking behind the brick running
into the structure. Without weep holes to drain the water to the outside,
flashing serves no purpose. Flashing and weepholes are required at
all brick shelf angles over all doors and windows. (1995 CABO 1 &
2 Family Dwelling Code, Sections 703.7.4 & 703.8)
-
Exterior wood not properly protected.
Some of the exterior wood has open joints which will allow moisture
to enter and will cause deterioration. Some of the paint is peeling
off the wood trim. The trim may not be properly primed to bond the
paint to the wood. Proper caulking and painting are needed. All exterior
walls shall be covered with approved materials designed and installed
to provide a barrier against the weather. (1995 CABO 1 & 2 Family
Dwelling Code, Section 703.1)
-
Exterior wood siding trim not properly
caulked or sealed at the brick or
concrete foundation walls to prevent water and moisture from damaging
the wood. Water will run behind the wood and cause deterioration.
(1995 CABO 1 & 2 Family Dwelling Code, Section 703.1)
-
Some of the exterior cement siding
has recessed nails. Recessed nails loose their holding
strength in fiber cement siding. All manufacturers require the nails
to be flush and not recessed. The recessed nails should be caulked
and another flush nail installed next to it. (1995 CABO 1 & 2
Family Dwelling Code, Section 108.1)
-
Exterior openings in the structure
are not sealed. This will allow air leaks into the
structure. All exterior joints in the building envelope, that are
sources of air leaks, shall be caulked, gasketed, weather-stripped
or otherwise sealed in an approved manner. (1995 CABO Model Energy
Code 502.3 & 602.3)
-
Chimney height is not tall enough.
This could be a potential fire hazard. All chimneys shall extend 2’
higher than any portion of roof within 10’ and at least 3’ higher
than the roof penetration. (1995 CABO 1 & 2 Family Dwelling Code,
Section 1004.1)
-
Roof shingles have toe board nail holes
present. Toe boards are walk boards the roofers use.
Any holes in the shingles could turn into a roof leak. All shingles
with holes should be replaced or sealed with a sealant that will last
as long as the shingles. Roof shingles shall provide a barrier against
the weather to protect its supporting elements and structure beneath.
(1995 CABO 1 & 2 Family Dwelling Code, Section 901.2)
-
Roof shingles are missing roofing felt
at the sheathing along the eaves. This protects the
roof sheathing. Slopes of 4 in 12 or greater, one layer of felt is
required over all of the roof decking. (1995 CABO 1 & 2
Family Dwelling Code, Section 902.2)
-
Step flashing is missing at sloped
vertical walls. Some of the roof
flashing at the vertical walls is continuous flashing. Flashing prevents
water from entering at the intersection of the wall and the roof.
Continuous flashing was used successfully for many years. However,
step flashing is a far superior method of flashing and is required
for all roofing. Flashing against a vertical sidewall shall be the
step-flashing method. (1995 CABO 1 & 2 Family Dwelling Code, Section
903.6)
-
Deck footings are smaller than the
minimum allowable size of 12" x 12".
See Figure 403.1a, note #5 and Table 502.3.3b. Footings shall
comply with Section 403. (1995 CABO 1 & 2 Family Dwelling Code,
Section 325.5)
-
Deck footings do not extend 12"
below grade. All footings must be
below the frost line. In no case shall exterior footings be less than
12 inches below grade. (1995 CABO 1 & 2 Family Dwelling Code,
Figure 403.1a, note #1.)
-
Deck stair handrail is not the correct
size. Handrails that are 2x4 or larger are too large
to be used for handrails since the cannot be gripped. Handrails shall
have either a circular cross section with a diameter of 1 1/4"
to 2", or a noncircular cross section with a perimeter dimension
of at least 4" but not more than 6 1/4" and a largest cross
section dimension not exceeding 2 3/4". Edges shall have a minimum
radius of 1/8". (1995 CABO 1 & 2 Family Dwelling Code, Section
315.2)
-
Exterior deck is missing properly installed
flashing. Flashing prevents water
from entering behind the deck and into the structure. Flashing is
required where decks attach to a wall or floor assembly of wood frame
construction. Exterior balconies, decks and porches shall be flashed
in accordance with Section 703.8. (1995 CABO 1 & 2 Family Dwelling
Code, Section 325.2.1)
-
Some of the roof framing has ridge
beams that are too small and do not extend to the
bottom of the rafters. The ridge must extend down to the bottom of
the rafters to properly support the rafters. The ridge shall not be
less in depth than the cut end of the rafters. (1995 CABO 1 &
2 Family Dwelling Code, Section 802.3)
-
Roof purlin supports, supporting the
rafters, are double 2x4s which are not the proper
size. The purlins should be single 2x6s turned perpendicular to the
rafters which are stronger and less expensive than flat double 2x4s.
Purlins shall be sized no less than the size of the rafters they support.
(1995 CABO 1 & 2 Family Dwelling Code, Section 802.4.1)
-
Some of the rafter purlins support
post exceed 48 inches apart. Additional support post
are required to properly support the purlins. All rafter purlins must
be braced every 48 inches to a load bearing wall or support. (1995
CABO 1 & 2 Family Dwelling Code, Section 802.4.1)
-
Some of the rafter purlins are spliced
between the support post. Support
members are not allowed to be spliced without additional support installed.
All purlins should be spliced directly above a support post. Purlins
must be continuous between braces (1995 CABO 1 & 2 Family Dwelling
Code, Figure 802.4.1)
-
Roof framing support members have "V"
joint or bird mouth splices that are not properly
reinforced or supported by a support post to a load bearing wall below.
All load bearing beams must be supported at any splice. Roof framing
shall be capable of supporting all loads imposed and shall transmit
the resulting loads to its supporting structural elements. (1995 CABO
1 & 2 Family Dwelling Code, Section 801.2)
-
Attic is missing flooring from the
end of the attic stairs to the furnace. This makes
it dangerous to climb over the stairs to access the flooring at the
furnace. All attics must have an unobstructed, floored passageway
22" wide x 30" high to the furnace. (1995 CABO 1 & 2
Family Dwelling Code, Section 1401.5) (2000 Standard Mechanical Code
306.3)
-
Attic insulation certification card
is missing. This is required to verify the attic has
the proper amount of insulation. The insulation installer shall provide
a signed and dated certification for the insulation installed, listing
the type of insulation, the manufacturer and the R-value. (1995 CABO
Model Energy Code Sect. 102.1.2)
-
Attic insulation thickness markers
are missing. One thickness marker is required every
300 s.f. of floor area. The thickness of roof/ceiling blown insulation
shall be identified by thickness markers. (1995 CABO Model Energy
Code Sect. 102.1.3)
-
Attic insulation is not deep enough.
Sometimes the insulation settles and is not deep enough. The insulation
installer certifies the minimum thickness of the insulation".
(1995 CABO Model Energy Code Sect. 102.1.2)
-
Attic is missing firestopping at an
open chase. A chase is an opening in the attic floor
that could allow a fire, from the story below, to enter the attic.
All openings in the attic floor need sealing with drywall. Firestopping
is required at each floor, at the attic floor and at all roof penetrations.
(1995 CABO 1 & 2 Family Dwelling Code, Section 602.7)
-
Basement ceiling needs firestopping
around all pipe penetrations. Firestopping prevents
a fire from spreading to different parts of the structure. Firestopping
is required at all openings around vents, pipes, ducts, chimneys and
fireplaces at ceiling and floor levels, with noncombustible materials.
(1995 CABO 1 & 2 Family Dwelling Code, Section 602.7)
-
Doors and windows are missing shims
and anchors along the jambs. All doors and windows
need shimming along the jambs (sides) and proper anchorage for a proper
installation. (1995 CABO 1 & 2 Family Dwelling Code, Section 108.1)
-
Bedroom windows not large enough to
be used for an emergency exit. Each bedroom shall
have an operable window with a sill height no more than 44" above
the floor. Minimum clear height of 22" or minimum width
of 20". The net clear opening shall be 4 square feet. (1995 CABO
1 & 2 Family Dwelling Code, Section 310.2)
-
Fireplace has wood trim within too
close to the opening. Wood too close to the opening
is a fire hazard and could catch fire. Woodwork or other combustible
materials shall not be placed within 6 inches of a fireplace opening.
Combustible material within 12 inches of the fireplace opening shall
not project more than1/8 inch for each 1 inch distance from such opening.
(1995 CABO 1 & 2 Family Dwelling Code, Section 1003.10)
-
Fireplace gas starter valve is not
accessible while lighting the starter. This
allows a dangerous build up of gas before being able to light the
burner. Fireplace gas starters must be within 4' of the valve. (1995
CABO 1 & 2 Family Dwelling Code, Section 2606.4)
-
Step heights or tread depths are not
the proper size. These are potential
trip hazards. The maximum allowable step height is 7 3/4". The
minimum allowed depth of the tread is 9". (1995 CABO 1 &
2 Family Dwelling Code, Section 314.2)
-
Step heights or tread widths vary in
a flight of stairs. The different step heights or
widths could be a trip hazard. Risers (heights) and treads (widths)
may not vary more than 3/8". (1995 CABO 1 & 2 Family Dwelling
Code, Section 314.2)
-
Stair tread nosing or overhang extends
too far over the step below. The
edge of the steps could break with the grain of the wood allowing
someone to fall down the stairs. The maximum allowable overhang is
1 1/4". (1995 CABO 1 & 2 Family Dwelling Code, Section 314.2.1)
-
Top basement step is not deep enough.
Sometimes the oak flooring overhangs the top tread too far. This is
a potential trip hazard. The minimum allowed depth of the tread is
9". (314.2). The maximum allowable projection or nosing is 1
1/4". (1995 CABO 1 & 2 Family Dwelling Code, Section 314.2.1)
-
Stairs are missing a 36" deep
landing at the bottom of the stairs between the bottom
step and the door. Any flight of stairs that are used for an emergency
exit must have a landing at the bottom before opening a door. A minimum
of 3 foot landing shall be required on each side of an egress door.
(1995 CABO 1 & 2 Family Dwelling Code, Section 312.1)
-
Door to the basement is missing a door
sweep and weather-stripping. Unconditioned air can
enter the conditioned space. Any opening from a conditioned space
to a non-conditioned space must be weather-stripped or sealed. (1995
CABO Model Energy Code 502.3 & 602.3)
-
Basement ceiling height is too low.
Basement ceiling ducts are too low and will prevent installing a ceiling
at the proper height. Habitable rooms shall have a ceiling height
of not less than 7 feet 6 inches. Furred areas shall have a ceiling
height of not less than 7 feet. (1995 CABO 1 & 2 Family Dwelling
Code, Section 305.1)
-
Garage floor does not slope enough
to prevent liquids from running under the walls. Flammable liquids
could run under the walls into the structure and be ignited by the
basement furnace or water heater. That area of floor used for parking
of automobiles or other vehicles shall be sloped to facilitate the
movement of liquids to a drain or toward the main vehicle entry doorway.
(1995 CABO 1 & 2 Family Dwelling Code, Section 309.3)
-
Garage furnace and water heater gas
piping is not protected from possible impact. An automobile
could hit the piping and cause a gas leak. The pipe must be protected
from possible impact. (2000 Standard Gas Code 305.4)
-
Ground fault circuit interrupter electrical
outlet is missing at
a wet location. Any electrical outlet located in the bathrooms, kitchen
counter area, unfinished basement, garage or on the exterior of the
structure that can be reached from the ground, must be GFCI protected.
(1999 NEC 210-8(6))
-
Ground fault circuit interrupter electrical
outlet is missing at a sink. Any electrical outlet
located within 6 feet of a sink or basin must be GFCI protected. (1999
NEC 210-8(b))
-
No heating and air conditioning damper
system present to balance the heating and air conditioning.
A two story structure with a single heat and air conditioning system,
will find it difficult to balance the heat and cooling. A readily
accessible manual or automatic damper system shall be provided to
partially restrict or shut off the heating and/or cooling input to
each zone or floor. (1995 CABO Model Energy Code 503.6.3.13 &
603.3.2.1)
-
Furnace ductwork not proper sealed
to prevent air leakage in nonconditioned areas. Sometimes
the duct insulation is sealed, but the actual ducts are not sealed.
All ducts must be sealed at the furnace and at the register boots.
All joints shall be securely fastened and sealed with welds,
gaskets, mastic adhesives, mastic-plus-embedded-fabric systems or
tapes. (1995 CABO 1 & 2 Family Dwelling Code, Section 1901.3.2)
(1994 Standard Mechanical Code 605.1)(2000 Standard Mechanical Code
603.8). Duct tape is not permitted as a sealant on any ducts. (1996
CABO Model Energy Code Sect. 503.8.2, 603.4)
-
Attic furnace does not have the required
working platform in front of the furnace for servicing.
This makes it difficult to service the unit or change the filter.
A working platform, 30" deep with a clear headroom of 30"
high, is required along the control side of the furnace. (1995 CABO
1 & 2 Family Dwelling Code, Section 1401.5)(1994 Standard Mechanical
Code 304.4)(2000 Standard Mechanical Code 306.3)
-
Range is missing anti-tip brackets
on the rear feet to prevent tipping over. All manufacturer’s
supply anti-tip brackets with all free standing ranges to prevent
tipping. A heavy object such as a turkey can be placed on the open
door causing the range to tip spilling hot liquids from the burners.
(1995 CABO 1 & 2 Family Dwelling Code, Section 108.1)